Duct Size Calculator (Australia, L/s and mm)
Size round duct in mm from a flow in L/s for an exhaust fan or a ducted air conditioning run: velocity, Pa/m loss, and rigid against flexible duct.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Duct Size Calculator?
A fan box quotes its flow with no duct attached. Whether a bathroom fan rated at 25 L/s still moves 25 L/s at the outlet depends on the duct it pushes through: its size, length and whether it is rigid or flexible. This calculator works out the speed and pressure loss for that duct. For the NCC minimum exhaust rates themselves, use the [air changes calculator](/en-au/air-changes-calculator).
Enter the flow in L/s, pick the duct material, and read the speed and pressure loss for the next standard size. The same sums work for ducted reverse-cycle systems, where insulated flexible duct to each outlet is the norm and its roughness roughly doubles the friction of a smooth pipe of the same size.
- Velocity and equal-friction sizing in US or metric units
- Darcy-Weisbach with Colebrook friction and five roughness categories
- Next standard round size in inch or EN 1506 metric series
- Rectangular equivalents from the Huebscher formula with aspect ratio
- Typical design velocity table and velocity pressure for fitting losses
Updated
How to use the Duct Size Calculator
- Choose SI and set the airflow unit to L/s.
- For an exhaust fan, use the velocity method at about 3 m/s; for a ducted system, use equal friction around 0.8 to 1 Pa/m.
- Select smooth for PVC or rigid metal duct, or flexible for flex duct pulled tight.
- Multiply the Pa/m by the run, add the grille and fittings, and compare with the fan's published curve.
Worked examples
Bathroom fan at 25 L/s
Input
25 L/s, 3 m/s target, smooth duct
Output
103.0 mm exact, so 125 mm (2.04 m/s, 0.55 Pa/m). A 100 mm duct runs at 3.18 m/s and 1.60 Pa/m
In 100 mm flexible duct the loss climbs to 3.57 Pa/m. Many ceiling fans have 100 or 150 mm spigots; a 150 mm flex run carries 25 L/s at 1.41 m/s and only 0.41 Pa/m.
Kitchen or laundry at 40 L/s
Input
40 L/s, 4 m/s target, smooth duct
Output
112.8 mm exact, 125 mm standard at 3.26 m/s and 1.26 Pa/m
A rangehood that ducts outside through 150 mm flex would run at 2.26 m/s and 1.04 Pa/m, so the larger flexible size costs no more pressure than the smaller rigid one.
Ducted reverse-cycle supply branch
Input
250 L/s, equal friction 1 Pa/m, flexible duct
Output
298.4 mm exact; a 300 mm flex branch runs at 3.54 m/s and 0.97 Pa/m, while 250 mm runs at 5.09 m/s and 2.56 Pa/m
The calculator rounds to the EN series (315 mm), but Australian flexible duct is usually stocked in 50 mm steps, so check the size you can buy directly.
Background and insight
The velocity method uses continuity alone: area equals airflow divided by velocity, so D = √(4Q/πV). It is simple and controls noise, but it ignores how much pressure the run will consume. The equal-friction method fixes the pressure loss per unit length instead, so every branch of a system loses pressure at a similar rate, which makes balancing easier. Residential designers commonly use 0.06 to 0.10 in.wg per 100 ft; ACCA Manual D derives the actual rate from the fan's available static pressure and the longest run.
Friction in a round duct follows the Darcy-Weisbach equation, Δp/L = (f/D)·ρV²/2. The friction factor f comes from the Colebrook equation, which depends on the Reynolds number and the relative roughness ε/D. ASHRAE classes galvanized steel ducts as medium smooth with ε = 0.09 mm (0.0003 ft), the basis of its friction chart, and lists smoother and rougher categories for other materials. Flexible duct, even fully stretched, is far rougher, and sagging or compressed flex can double the loss again.
A rectangular duct does not have the same friction as a round duct of equal area, because its corners add wetted perimeter. Huebscher (1948) gave the equivalent diameter that carries the same airflow at the same friction: De = 1.30 (ab)^0.625 / (a + b)^0.25. A 12 x 12 in duct is equivalent to 13.1 in round, not the 13.5 in its area would suggest. Aspect ratios above about 4:1 waste metal and pressure, and are best avoided.
Common use cases
Residential duct layouts
Size trunks and branch runs for a furnace or heat pump from room airflows and a target friction rate.
Ventilation and extract systems
Pick duct sizes for an MVHR unit, a bathroom fan run or a kitchen extract in metric or US units.
Swapping round for rectangular
Find a rectangular section that fits a ceiling void or joist bay without losing airflow or adding friction.
Checking an existing duct
Enter the airflow and see what friction and velocity a given round size produces, to explain noise or low airflow.
Tips and limitations
- Ducts that pass through a roof space and are left loose or kinked lose much more than the figures here; pull flex tight and support it.
- Commercial and apartment buildings follow NCC Volume One and AS 1668.2, which use their own design rates.
- Keep the exhaust outlet clear of openable windows and air intakes so stale air does not come straight back in.
Sources and further reading
- NCC 2025 Housing Provisions, Part 10.8 Condensation management (10.8.2 Exhaust systems), Australian Building Codes Board. Minimum exhaust flow rates, discharge to outdoor air and the 10-minute run-on for bathroom fans.
- Handbook: Indoor air quality, section 4.3 (local and general exhaust, air distribution), Australian Building Codes Board. Why bathrooms and laundries use general exhaust, and how placing exhaust and supply too close short-circuits the airflow.
Frequently asked questions
Should a bathroom fan duct be 100 mm or 150 mm?
At 25 L/s a 100 mm smooth duct runs at 3.18 m/s and loses about 1.6 Pa/m, and 100 mm flexible duct about 3.57 Pa/m. A 150 mm flex run carries the same flow at 1.41 m/s and 0.41 Pa/m, so for anything but a short run the larger duct keeps the fan near its rated flow.
How much more does flexible duct lose per metre?
Pulled tight, flexible duct loses roughly twice as much as smooth rigid duct of the same size at the same flow. Sagging or kinked flex loses far more, so support it and keep it straight.
What duct size do I need for a 25 L/s exhaust fan?
A 100 mm smooth duct works for short runs (3.18 m/s, about 1.6 Pa/m). For longer runs or flexible duct, 125 or 150 mm keeps the loss low enough that the fan still delivers its rated flow.
How do I convert m³/h to L/s for an Australian fan?
Divide by 3.6: a fan rated at 90 m³/h moves 25 L/s at zero back pressure. Check the fan curve at the pressure your duct creates.
What exhaust rate does a bathroom fan need?
The NCC minimum exhaust rates for bathrooms, kitchens and laundries, and the discharge and run-on rules, are covered on the [air changes calculator](/en-au/air-changes-calculator). Size the duct here for the flow you choose.
Is there an in-depth guide to the Duct Size Calculator?
Yes. “Duct Sizing: The Velocity and Equal-Friction Methods Explained” covers the background, how it works, common pitfalls and worked examples. Read the full guide.