Pakistan version. Gives the generator size in kVA at the rated power factor and the current at 230 V, Pakistan's nominal supply, starting from a house list with a water motor. US version
Generator Size Calculator for Load Shedding (Pakistan)
Size a petrol or gas generator in kVA for load shedding from your appliance list, with the water motor and AC starting surge and the current at 230 V.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Generator Size Calculator?
When the feeder goes off, the generator has to start whatever is running, including the motor that fills the overhead tank. Tick the appliances you want on during load shedding and the calculator adds their running watts, adds the largest starting surge, and divides by the generator's rated power factor (kW ÷ kVA on its plate) to give the minimum kVA. The current is shown at 230 V.
The default list is a typical house: refrigerator, deep freezer, LED lights, TV and router, chargers and a 1/2 hp water motor. Together they run at 2 650 W; the refrigerator's start is the largest surge, the peak is 4 150 W and the minimum rating is 5.19 kVA at a 0.8 power factor. Switch on the 1 ton split AC row, entered at 1 200 W running and 3 600 W starting, and the minimum rises to 7.81 kVA.
NEPRA's Performance Standards (Distribution) Rules set the nominal supply at 400/230 V and 50 Hz, and list the order in which distribution companies shed load: rural consumers and urban residential consumers on separate feeders come first. A house on such a feeder should plan for outages as a matter of routine, and size the generator for the loads that really must run.
- Editable appliance list with running and starting watts and quantities
- Typical wattages for common household and job-site loads
- Largest-start method with adjustable headroom
- Optional credit for the generator's surge rating
- Suggested common generator size and current at 120/240 V, or at the supply voltage you enter
- Minimum kVA rating from the generator's rated power factor (0.8 by default)
Updated
How to use the Generator Size Calculator
- Untick anything that will not run during the outage or job, and set quantities.
- Replace typical wattages with nameplate values where you can. For a motor without a starting figure, use two to three times the running watts.
- Add loads from the typical list or as custom lines.
- Choose headroom on the running load (20 to 25% is usual) and whether to count the generator's own surge rating.
- Read the running total, peak at motor start, minimum rated output and the suggested generator size.
Worked examples
House with a 1/2 hp water motor
Input
Refrigerator 700/2 200 W, deep freezer 500/1 500 W, LED lights 100 W, TV and router 250 W, chargers 100 W, water motor 1/2 hp 1 000/2 100 W; 20% headroom; PF 0.8; 230 V
Output
Running 2 650 W (11.5 A at 230 V); peak 4 150 W; minimum 5.19 kVA; suggested 5 kW
The refrigerator's start (1 500 W above running) is larger than the water motor's (1 100 W), so it sets the peak. Run the water motor before the refrigerator restarts, or after it settles, and the surges will not overlap.
Adding a 1 ton split AC
Input
The list above plus a 1 ton split AC entered at 1 200/3 600 W
Output
Running 3 850 W (16.7 A); peak 6 250 W; minimum 7.81 kVA; suggested 6.5 kW
The AC compressor's start adds 2 400 W. If the generator's data sheet allows a short surge 20% above its rating, the minimum drops to 5 208 W (6.51 kVA); choose the "+20%" option only when the maker states it. If your AC is an inverter model, replace 1 200/3 600 W with the running and starting figures from its data sheet.
Essentials only
Input
Refrigerator, LED lights, TV and router, chargers; 20% headroom; PF 0.8; 230 V
Output
Running 1 150 W (5.0 A); peak 2 650 W; minimum 3.31 kVA; suggested 3 kW
For lights, a refrigerator and the TV, a small generator is enough; the size is set by the refrigerator starting, not by the running load.
Background and insight
Resistive loads such as heaters, kettles and incandescent lights draw the same power when they switch on as when they run. Induction motors in compressors, pumps and fans draw several times their running current for a second or two while they accelerate, which shows up as starting watts. The generator must ride through that surge without its voltage collapsing.
The largest-start method assumes motors start one at a time, so it adds only the biggest surge: required watts = sum of running watts + max(starting − running). For a refrigerator (700 W running, 2,200 W starting), a 1/2 hp sump pump (1,050 / 2,150 W), a furnace blower (800 / 2,350 W), lights and electronics, the running total is 2,900 W and the furnace blower adds the biggest surge of 1,550 W, so the peak is 4,450 W and a 5,000 W generator fits. Typical wattages here are drawn from generator makers' worksheets and vary a lot between models, so nameplate figures (watts = volts × amps) always win.
Portable generators list a running (rated) and a higher surge (starting) wattage; inverter models typically surge 10 to 30% above rating for a few seconds. Home standby units are rated in kW at 0.8 power factor and quote motor-starting ability separately. By default this calculator does not count on any surge rating, the conservative choice; you can let it use a 20% or 50% surge margin. However you connect it, the NEC requires transfer equipment for optional standby systems (702.5) so the generator cannot back-feed the utility line.
Common use cases
Buying a portable generator
Pick a size that keeps the fridge, sump pump and furnace running in an outage without tripping.
Specifying home standby
Compare essential-circuit and whole-house loads before talking to an installer.
Job-site power
Check that a generator can start a compressor while saws and lights are running.
RV and camping
See whether a 2,000 W inverter generator can start the rooftop air conditioner.
Tips and limitations
- Add ceiling fans and other loads you run during outages as custom rows, using the watts on their plates.
- Read the kW and kVA on the generator's plate; their ratio is the power factor to enter, so different sets can be compared fairly.
- Do not put an electric geyser, iron or heater on a small generator; heating loads use more than everything else on the list together.
- Run the generator outdoors, away from windows, doors and ventilators, because of carbon monoxide.
Sources and further reading
- NEPRA Performance Standards (Distribution) Rules, 2005, with amendments, NEPRA. Nominal 400/230 V within ±5% for at least 95% of consumers, 50 Hz ±1%, and the priority order for load shedding.
- IEC 60038 IEC standard voltages, International Electrotechnical Commission. Standard voltage values for the nominal voltage of electricity supply systems.
Frequently asked questions
What size generator do I need for my house?
For a refrigerator, lights, TV and router, about 3.3 kVA. With a deep freezer and a 1/2 hp water motor it is about 5.2 kVA, and adding a 1 ton split AC entered at 1 200/3 600 W takes it to about 7.8 kVA at a 0.8 power factor. Put your own appliances in the list for a real answer.
How do I convert kVA to kW for a generator?
Multiply kVA by the generator's rated power factor. At 0.8, a 5 kVA set gives 4 kW. Going the other way, the calculator divides the minimum watts by the power factor to give the kVA rating you need.
Why is the current shown at 230 V?
NEPRA's Performance Standards (Distribution) Rules set 400/230 V as the nominal low-voltage supply, and require distribution companies to keep at least 95% of consumers within ±5% of nominal. A household single-phase supply is 230 V.
Which areas face load shedding first?
The rules list the order: supply to rural consumers and to urban residential consumers on separate feeders first, then other non-industrial urban consumers, then agriculture on dedicated supplies, industry, schools and hospitals, and defence and strategic installations last. Distribution companies rotate outages within each group.
Do I need a changeover switch?
Yes, if the generator feeds the house wiring. A changeover switch, installed by a qualified electrician, keeps the generator and the distribution company's supply apart so the generator cannot feed back into the lines while they are being worked on.
Will a 5 kVA generator run an AC?
A 1 ton split AC drawing 1 200 W running and 3 600 W at start, on its own, yes: it needs 4.5 kVA at a 0.8 power factor. With a refrigerator, deep freezer and water motor running as well, the AC's start pushes the peak to about 6 250 W, which needs about 7.8 kVA at a 0.8 power factor unless the set is rated for a short surge.
Is there an in-depth guide to the Generator Size Calculator?
Yes. “What Size Generator Do I Need? Running Watts, Surge and Headroom” covers the background, how it works, common pitfalls and worked examples. Read the full guide.