Air Changes and Principal Ventilation Fan Calculator (Canada)
Size the principal ventilation fan or HRV by bedrooms under NBC 9.32.3.3, convert bathroom and kitchen fan L/s and cfm to air changes per hour for a room.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Air Changes per Hour Calculator?
In a Canadian house the heating-season ventilation under Part 9 is built around a principal ventilation fan, often the exhaust side of an HRV, sized by the number of bedrooms rather than by air changes. NBC 2025 Table 9.32.3.3 gives a normal operating exhaust capacity of 16 to 24 L/s for one bedroom, rising to 22 to 32 L/s for three and 30 to 45 L/s for five. Houses with more than five bedrooms must follow good practice such as CSA F326 (Clause 9.32.3.1.(1)(a)).
Supplemental fans come on top: at least 50 L/s in the kitchen (9.32.3.7) and 25 L/s in any bathroom that the principal fan does not draw from. Fan boxes sold in Canada usually quote cfm, so the calculator shows L/s and cfm together; 25 L/s is 53 cfm and 50 L/s is 106 cfm.
Air changes per hour still appear in the code for summer. A habitable room with no openable window and no air conditioning needs a non-heating-season fan able to move one air change per hour (9.32.2.3.(3)).
- ACH from airflow or airflow from a target ACH
- Room volume from dimensions or entered directly, in feet or metres
- Airflow in cfm, m³/h and L/s together
- ASHRAE 62.2 whole-house ventilation rate from floor area and bedrooms
- Guidance table from CDC, ASHRAE 62.2, ASHRAE 170 and IECC with sources
Updated
How to use the Air Changes per Hour Calculator
- Keep the units on metric, or switch to US units for feet and cfm.
- For a fan, choose "ACH from airflow" and enter its rating in m³/h (L/s times 3.6).
- For the one air change per hour summer rule, choose "Airflow for target ACH" and enter 1.
- In the ventilation panel, keep the NBC rule and enter the number of bedrooms and the floor area.
Worked examples
Principal fan for a three-bedroom house
Input
3 bedrooms, 155 m² (about 1,670 ft²) with 2.4 m ceilings
Output
22 to 32 L/s (46.6 to 67.8 cfm); about 0.21 ACH at the minimum
Table 9.32.3.3 sets a range, not a single figure: the fan or HRV must run continuously within it. The whole-house air change rate that results is low, which is why the code relies on bedroom-based rates rather than ACH.
Bathroom fan in air changes
Input
Bathroom 2.4 x 1.5 x 2.4 m, supplemental fan 25 L/s (90 m³/h)
Output
8.6 m³; 10.4 ACH; 53 cfm
25 L/s is the minimum rated capacity where the principal fan has no intake in that bathroom. A long duct run or a cheap fan with high static losses will deliver less than its rating.
Summer ventilation for a basement rec room
Input
Rec room 8 x 6 x 2.3 m with no openable window and no air conditioning, target 1 ACH
Output
110.4 m³; 30.7 L/s (65 cfm)
Sentence 9.32.2.3.(3) asks for one air change per hour in this case. In heating season the same room falls under the principal ventilation system.
Background and insight
ACH is a convenient way to compare rooms of different sizes, but it is not how every standard sets ventilation. ASHRAE 62.1 for commercial buildings gives outdoor air per person plus per square foot of floor, and ASHRAE 62.2 for homes uses 0.03 cfm per square foot of floor area plus 7.5 cfm for each occupant, counting bedrooms plus one. A 1,500 ft² three-bedroom house needs 75 cfm of continuous ventilation, which is only about 0.35 ACH.
Higher figures appear where airborne contaminants matter. In 2023 the CDC and NIOSH recommended aiming for 5 or more air changes per hour of clean air in occupied rooms, counting outdoor air, filtered return air and portable air cleaners together. Healthcare design under ASHRAE 170 sets 12 ACH for new airborne infection isolation rooms and 20 total ACH for operating rooms. Kitchens and bathrooms in homes get local exhaust under 62.2: a 100 cfm range hood or 5 ACH continuous for kitchens, and 50 cfm intermittent or 20 cfm continuous for bathrooms.
ACH50, measured with a blower door at 50 Pa, is a different number entirely. It describes airtightness under test pressure, not ventilation, and the 2021 IECC limits new homes to 3 ACH50 in most climate zones. Natural infiltration under normal conditions is a small fraction of the ACH50 value. With perfect mixing, each air change removes 63% of a contaminant, so 99% removal takes about 4.6 air changes.
Common use cases
Sizing portable air cleaners
Check whether a HEPA unit's CADR delivers 5 ACH in a classroom, office or bedroom, or how many units a large room needs.
Bathroom and kitchen fans
Turn a room volume into the fan cfm needed for a target number of air changes, then compare with the 62.2 minimums.
Whole-house ventilation
Get the ASHRAE 62.2 continuous rate for an ERV, HRV or exhaust-only system in a new or retrofitted home.
Workshops and spray booths
Estimate the extract airflow for a target ACH, then confirm against the solvent or dust guidance that applies.
Tips and limitations
- The principal fan needs a manual switch in the living area marked "VENTILATION FAN" (9.32.3.3.(5)).
- A kitchen can skip its 50 L/s fan only if the principal fan can switch to 2.5 times its minimum capacity from a "KITCHEN EXHAUST" switch (9.32.3.7.(3)).
- Fuel-fired space- or water-heating appliances that are not direct-vented or mechanically vented bring in the depressurization rules of 9.32.3.8; check them before adding big exhaust fans.
Sources and further reading
- National Building Code of Canada 2025, National Research Council Canada. NRC Publications Archive (free PDF). Division B, Subsection 9.32.2 (Table 9.32.2.3 and Sentence (3)), 9.32.3.1, 9.32.3.3 (Table 9.32.3.3), 9.32.3.7 and 9.32.3.8.
- National Building Code of Canada 2025 (catalogue record), Government of Canada Publications
Frequently asked questions
How do I size an HRV for my house in Canada?
Under NBC 2025 Part 9, the principal ventilation fan, which can be the exhaust side of an HRV, must be capable of the Table 9.32.3.3 normal operating exhaust capacity for the number of bedrooms: 16 to 24 L/s for 1, 18 to 28 for 2, 22 to 32 for 3, 26 to 38 for 4 and 30 to 45 for 5. Most provinces still enforce an earlier edition, so check the one adopted where you build.
What size bathroom fan does the building code require?
A supplemental exhaust fan of at least 25 L/s (53 cfm) in each bathroom or water-closet room where the principal ventilation fan has no exhaust intake (9.32.3.7.(4)). It must have a manual switch in the room.
What size kitchen exhaust fan do I need?
At least 50 L/s (106 cfm), unless the principal fan draws only from the kitchen, or it draws from the kitchen and other rooms and can be switched to 2.5 times its minimum rate from a switch marked "KITCHEN EXHAUST".
Does the code require a number of air changes per hour?
Not for heating-season ventilation, which is sized by bedrooms. The one air change per hour figure applies in the non-heating season to habitable rooms without natural ventilation that are not mechanically cooled (9.32.2.3.(3)).
How many cfm is 1 L/s?
1 L/s is 2.119 cfm, and 1 cfm is 0.472 L/s. Multiply L/s by 3.6 to get m³/h.
Is there an in-depth guide to the Air Changes per Hour Calculator?
Yes. “Air Changes per Hour: What ACH Means and How Much Ventilation You Need” covers the background, how it works, common pitfalls and worked examples. Read the full guide.