United Kingdom version. Millimetres, and checks against Approved Document K for a private stair in England: rise 150 to 220 mm, going 220 to 300 mm, pitch 42° and 2R + G of 550 to 700 mm. US version

Stair Calculator (UK, Approved Document K)

Risers, goings, pitch and stringer length in mm from the floor-to-floor height, checked against Approved Document K: 220 mm rise, 220 mm going and 42 degrees.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Stair Calculator?

In England, stairs in a house follow Approved Document K. For a private stair, Table 1.1 allows any rise from 150 to 220 mm with any going from 220 to 300 mm, but the pitch must not exceed 42°, and twice the rise plus the going should fall between 550 and 700 mm. Headroom is at least 2.0 m, reduced for loft conversions to 1.9 m at the centre of the stair.

The trap is that the two maximums do not work together. With a 220 mm rise and a 220 mm going the pitch is 45°, so a 2.6 m floor-to-floor height split into 12 risers of 216.7 mm on 220 mm goings passes the rise and going limits but fails the 42° pitch. Thirteen risers of 200 mm on 225 mm goings comes in at 41.6°.

Enter the floor-to-floor height in mm, the most you want each riser to be, and either the going or the space available for the flight. The tool works out the risers and goings, the total run, the pitch and the stringer length, and checks each against Part K.

  • Risers, treads, total run, stringer length and angle from the total rise
  • Checks against IRC R311.7 riser, tread and nosing limits, plus 2R + T comfort
  • Fit-to-run mode for stairs in a fixed space
  • Scale side-view drawing and one-more, one-fewer riser comparison
  • Inches or millimetres; copy the layout or share a link
Read the guide: Roof Pitch, Stair Layout, AC Sizing and Running Costs Explained

Updated

How to use the Stair Calculator

  1. Measure from finished floor to finished floor, allowing for the flooring you will lay.
  2. Set the maximum riser height; 200 mm or less makes the 42° pitch easier to meet.
  3. Enter the going, or the available run if the stair must fit a fixed length of hall.
  4. Read the checks. If the pitch fails, add a riser or lengthen the going.

Worked examples

Maximum rise and going together fail on pitch

Input

Total rise 2,600 mm, maximum riser 220 mm, going 220 mm

Output

12 risers of 216.7 mm, 11 goings of 220 mm; pitch 44.6°; 2R + G = 653 mm

Every dimension is inside Table 1.1 except the pitch, which is above the 42° limit for a private stair.

A compliant flight for the same height

Input

Total rise 2,600 mm, maximum riser 200 mm, going 225 mm

Output

13 risers of 200 mm, 12 goings of 225 mm; run 2,700 mm; pitch 41.6°; stringer 3,748 mm

One extra riser costs 280 mm more run in the hall but gives an easier stair that meets every Part K check.

A loft conversion stair in a tight space

Input

Total rise 2,350 mm, maximum riser 220 mm, available run 2,400 mm

Output

11 risers of 213.6 mm, 10 goings of 240 mm; pitch 41.7°; 2R + G = 667 mm

Fitting the flight into 2.4 m works here. Squeeze it to 2.2 m and each going drops to 220 mm, which pushes the pitch to 44.2°, so a winder or a different position is needed.

Background and insight

The code numbers come from IRC section R311.7: R311.7.5.1 limits riser height to 7 3/4 inches (196 mm), R311.7.5.2 sets a 10 inch (254 mm) minimum tread, R311.7.2 requires 6 feet 8 inches of headroom measured from the sloped line of the nosings, and riser heights within a flight may differ by no more than 3/8 inch. Commercial stairs under the IBC are stricter, at a 7 inch maximum riser and 11 inch minimum tread, and local amendments are common, so confirm with your building department.

The 2R + T rule goes back to François Blondel, a 17th-century French architect who tied step size to the length of a natural stride; modern practice puts the target at 24 to 25 inches (610 to 635 mm). A 7 inch riser with an 11 inch tread scores 25, a classic comfortable stair. Steeper stairs save floor space but feel abrupt going down, which is when most stair falls happen.

Common use cases

  • Deck and porch stairs

    Lay out stringers for the drop from a deck to grade, with the riser count and cut dimensions.

  • Basement and loft stairs

    Check whether a replacement stair will fit the existing opening and pass inspection.

  • Planning a renovation

    See how much floor space a new stair needs before moving walls.

  • Checking an existing stair

    Measure a stair that feels steep and see which rule it breaks.

Tips and limitations

  • Rise and going must be the same on every step in a flight; measure from the nosing, as Diagram 1.1 of Approved Document K shows.
  • Open risers in a dwelling must stop a 100 mm sphere passing through, and treads should overlap by at least 16 mm.
  • Scotland, Wales and Northern Ireland have their own building standards for stairs, so check those if you are not in England.

Sources and further reading

  1. Approved Document K: protection from falling, collision and impact, GOV.UK. Table 1.1 rise and going, 42° pitch, 2R + G, headroom Diagrams 1.3 and 1.4.
  2. Approved Document K, 2013 edition (PDF), Ministry of Housing, Communities and Local Government

Frequently asked questions

What is the maximum stair rise in the UK?

For a private stair in a dwelling in England, Approved Document K allows a rise of 150 to 220 mm. The going must be 220 to 300 mm, and the pitch no steeper than 42°, which in practice keeps most house stairs nearer 200 mm.

What is the 42 degree rule for stairs?

Approved Document K sets 42° as the maximum pitch of a private stair. Pitch is the angle of the line joining the nosings, so it depends on rise and going together: a 200 mm rise on a 225 mm going is 41.6°, a 216.7 mm rise on 220 mm is 44.6° and fails.

What does 2R + G mean in Part K?

Twice the rise plus the going. Approved Document K says the normal relationship is between 550 and 700 mm. A 200 mm rise and a 225 mm going give 625 mm.

How much headroom does a loft conversion stair need?

Normally 2.0 m above the pitch line. Where a loft conversion cannot achieve that, Diagram 1.4 of Approved Document K accepts 1.9 m at the centre of the stair, falling to 1.8 m at the side.

How many stairs do I need for a 2.6 metre ceiling height?

It depends on the floor-to-floor height, not the ceiling height alone: add the floor thickness. For 2,600 mm floor to floor, 13 risers of 200 mm is a common answer and meets Part K with a 225 mm going.

Does a replacement staircase need building regulations approval?

Replacing a stair like for like is often repair work, but a new stair, a changed layout or a loft conversion stair is controlled work. Your council building control or an approved inspector can confirm before you start.

Is there an in-depth guide to the Stair Calculator?

Yes. “Roof Pitch, Stair Layout, AC Sizing and Running Costs Explained” covers the background, how it works, common pitfalls and worked examples. Read the full guide.