Three-Phase Power Calculator (South Africa, 400/230 V)

Convert kVA, kW and motor kW to amps on a 400 V three-phase or 230 V single-phase supply, and check a load against an Eskom 25, 50 or 100 kVA supply size.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Three-Phase Power Calculator?

Eskom describes its low-voltage networks as normally supplying 400/230 V three-phase or 230 V single-phase, at 50 Hz. This version therefore opens on 400 V line to line. Give it a current, a kVA or kW figure, or a motor's rated output in kW, and it returns the current in each line together with kW, kVA and kVAr.

The kVA figure is the one to watch in South Africa, because supplies are sold by size in kVA. The Eskom tariff booklet lists three-phase residential and business supplies of 25 kVA (40 A per phase), 50 kVA (80 A per phase) and 100 kVA (150 A per phase), and a single-phase supply of 16 kVA (80 A). Before adding a borehole pump, a kiln or a second geyser circuit, check that the new total still fits the supply.

For motors, enter the shaft output from the rating plate and the plate efficiency and power factor. The calculator divides by the efficiency first, so an 11 kW motor at 90% efficiency shows the 12.2 kW it actually takes from the DB board.

  • Single-phase and three-phase, line-to-line or line-to-neutral voltage
  • Solve from amps, kW, kVA or horsepower
  • Power factor, efficiency, kVAR and phase angle
  • Comparison table of current at other power factors
  • Formula panel with your numbers, copy and share
Read the guide: The Three-Phase Power Formula: Where √3 Comes From

Updated

How to use the Three-Phase Power Calculator

  1. Pick single-phase, three-phase with line-to-line voltage, or three-phase with line-to-neutral voltage.
  2. Enter the voltage. The preset buttons cover common systems such as 208, 400, 480 and 600 V line to line or 120, 230 and 277 V line to neutral.
  3. Choose what you know: current, kW, kVA or motor horsepower, and type the value.
  4. Enter the power factor (1 for resistive heaters, 0.8 to 0.9 for loaded induction motors) and, for motors, the nameplate efficiency.
  5. Read current, kW, kVA, kVAR and shaft output, and check the formula panel to see the numbers substituted.

Worked examples

What a 25 kVA three-phase supply allows

Input

3-phase 400 V line to line, 25 kVA, PF 1

Output

36.08 A per line

Eskom pairs the 25 kVA three-phase size with 40 A per phase. Entering 40 A at 400 V gives 27.7 kVA, so the breaker is not the whole story: your notified maximum demand is the kVA figure, and that is what the supply size is sold and charged on.

11 kW irrigation pump motor

Input

3-phase 400 V, motor rated output 11 kW, PF 0.86, efficiency 90%

Output

20.51 A per line; 12.22 kW drawn, 14.21 kVA, 7.25 kVAr

On a 25 kVA farm supply this one motor uses more than half the capacity while running, before its starting current. The pump supplier's starting method (direct-on-line, star-delta or a soft starter) decides whether the supply can take the start.

Single-phase 16 kVA house supply

Input

Single-phase 230 V, 16 kVA, PF 1; then 80 A

Output

69.57 A for 16 kVA; 18.4 kVA at 80 A

The tariff booklet lists the single-phase Homepower 4 and Homeflex 4 size as 16 kVA (80 A per phase). If an inverter, a stove and a geyser all run together, add their watts and compare the total with 16 kVA, not with the 80 A label.

Moving up to a 50 kVA supply

Input

3-phase 400 V, 50 kVA, PF 1

Output

72.17 A per line

A business or smallholding outgrowing 25 kVA usually looks at the 50 kVA (80 A per phase) size next. The calculator shows the balanced current; if one phase carries most of the single-phase loads, it will trip first.

Background and insight

For a balanced three-phase load the apparent power is S = √3 × V(LL) × I, where V(LL) is the line-to-line voltage and I the current in each line. The √3 comes from the 120° spacing of the phases: the voltage between two lines is √3 times the voltage from a line to neutral, and three phases each carry V(LN) × I, so S = 3 × V(LN) × I = √3 × V(LL) × I. Single-phase is simply S = V × I.

Real power, the part that does work and that a kWh meter bills, is P = S × PF. Reactive power, which circulates between the supply and the magnetic fields of motors and transformers, is Q = S × sin φ, where φ = arccos PF. Cables, breakers and transformers must carry the full current, so they are rated in amps or kVA, not kW. A 100 A load at 480 V and PF 0.85 is 83.1 kVA but only 70.7 kW.

Motor nameplates give output power in horsepower or kW at the shaft. The electrical input is the output divided by efficiency, so a 10 hp motor (7.457 kW) at 90% efficiency draws 8.29 kW from the supply. One horsepower is 745.7 W (NIST SP 811). For wiring and protection the NEC uses its own full-load current tables (430.248 for single-phase, 430.250 for three-phase) rather than nameplate amps, because they are deliberately conservative.

Common use cases

  • Feeder and breaker checks

    Convert a kW or kVA schedule into amps to choose cables, breakers and busbars.

  • Motor circuits

    Estimate the running current of a pump, fan or compressor from its horsepower, efficiency and power factor.

  • Generator and UPS loading

    Turn measured amps into kVA and kW to compare with a generator or UPS rating.

  • Reading meter data

    Make sense of a power analyser reading by relating amps, kW, kVA and kVAR.

Tips and limitations

  • Spread single-phase loads (geysers, stoves, plug circuits) over the three phases. The formula assumes a balanced load; one overloaded phase can trip while the others are lightly used.
  • For motors use "Motor rated output (kW)". Typing the plate kW as real power understates the current by the efficiency, around 10% on an 11 kW motor.
  • If a drawing or nameplate says 380/220 V, enter the voltage it gives; the difference from 400 V is about 5% in current.
  • Check the supply size on your Eskom or municipal account before buying three-phase equipment: the kVA is printed on the tariff, not on the meter box.

Sources and further reading

  1. Connection charges for customers connected to Eskom's distribution network (procedure), Eskom Distribution. Definitions: LV networks normally supply at 400/230 V three-phase or 230 V single-phase; MV reticulation is normally 11 or 22 kV.
  2. Tariffs and Charges Booklet 2026/2027, Eskom Distribution. Supply sizes: single-phase 16 kVA (80 A), three-phase 25 kVA (40 A), 50 kVA (80 A) and 100 kVA (150 A) per phase.
  3. SANS 1019:2021 Standard voltages, currents and insulation levels for electricity supply, South African Bureau of Standards. Scope: standard voltages and currents for a.c. systems with a nominal frequency of 50 Hz, based on IEC 60038.
  4. Management of certificates of compliance for electrical installations (240-170000465, revision 3), Eskom Distribution. Who may sign Certificates of Compliance for single-phase and three-phase installations.

Frequently asked questions

Is the supply in South Africa 400 V or 380 V?

Eskom's connection charges procedure describes low-voltage networks as normally supplying 400/230 V three-phase or 230 V single-phase. If a drawing or nameplate says 380/220 V, enter that value instead. SANS 1019 sets South Africa's standard voltages for 50 Hz systems, based on IEC 60038.

How many amps is a 25 kVA three-phase supply?

At 400 V, 25 kVA is 36.1 A per line. The Eskom tariff booklet lists the 25 kVA three-phase size as 40 A per phase, which at 400 V would be 27.7 kVA. Plan your load on the kVA size of the supply.

Will an 11 kW pump run on my farm supply?

Running, it draws about 20.5 A per line and 14.2 kVA at a plate efficiency of 90% and power factor of 0.86. Whether it fits depends on what else runs at the same time and on how it starts; direct-on-line starting draws several times the running current for a few seconds.

What is the difference between kVA and kW on my Eskom account?

kVA is the size of the supply and what network capacity charges are based on; kWh is the energy you pay per unit for. kW = kVA × power factor, so a load with a poor power factor uses more of your kVA for the same work.

Do I need to convert kW motor ratings to horsepower?

No. Motors sold in South Africa are rated in kW of shaft output, which the calculator takes directly. Use the horsepower option only for older or imported North American equipment.

Can I use this to choose a cable size?

It gives the design current, which is where cable selection starts. The installation itself must comply with SANS 10142-1 and be signed off with a Certificate of Compliance by a registered person, so have the circuit designed by a registered electrician.

Is there an in-depth guide to the Three-Phase Power Calculator?

Yes. “The Three-Phase Power Formula: Where √3 Comes From” covers the background, how it works, common pitfalls and worked examples. Read the full guide.