United Kingdom version. Starts at 400 V three-phase, 50 Hz, takes motor ratings in kW as on IEC nameplates, and explains the 230 V +10%/-6% supply tolerance set by the ESQCR. US version
Three-Phase Power Calculator (UK, 400 V)
Convert kW, kVA and motor kW ratings to amps on a 400 V three-phase or 230 V single-phase supply, with power factor, efficiency and the UK voltage tolerance.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Three-Phase Power Calculator?
British supplies are 230 V from line to neutral and 400 V between lines, at 50 Hz, so this version opens on 400 V three-phase. Type a current, a kW or kVA figure, or the rated output of a motor in kW straight off its plate, and the line current, kVA and kVAR follow. A 7.5 kW motor that is 90% efficient at power factor 0.84 draws 14.3 A in each line.
Motors sold in the UK are rated by shaft output in kW, which is not what the supply delivers. The calculator divides the rated output by the efficiency before working out the current, so you are not caught out by the gap between the 7.5 kW on the plate and the 8.33 kW the motor actually takes from the board.
It also helps when you are choosing between a single-phase and a three-phase connection for something like an EV charger, a large electric shower or a workshop compressor. The same power spread across three lines needs much less current in each conductor than it would on one 230 V line.
- Single-phase and three-phase, line-to-line or line-to-neutral voltage
- Solve from amps, kW, kVA or horsepower
- Power factor, efficiency, kVAR and phase angle
- Comparison table of current at other power factors
- Formula panel with your numbers, copy and share
Updated
How to use the Three-Phase Power Calculator
- Leave the system on 3-phase line to line at 400 V for a normal three-phase board, or switch to single-phase at 230 V for a domestic circuit.
- Choose what you know. For a motor, pick "Motor rated output (kW)" and type the figure on the rating plate.
- Enter the power factor and efficiency from the rating plate or the maker's data sheet rather than a rule of thumb; both fall when a motor runs well below full load.
- Read the current per line, kW drawn, kVA and kVAR, then open the working to see each step with your numbers.
Worked examples
7.5 kW motor on a 400 V board
Input
3-phase 400 V line to line, motor rated output 7.5 kW, PF 0.84, efficiency 90%
Output
14.32 A per line; 8.33 kW drawn, 9.92 kVA, 5.38 kVAR
The supply provides 7.5 ÷ 0.90 = 8.33 kW, and 8.33 ÷ 0.84 = 9.92 kVA. Dividing by √3 × 400 V gives 14.3 A. Starting current is several times higher, which is why the motor maker's data, not this running figure, decides the protective device curve.
EV charger: 7.4 kW single-phase or 11 kW three-phase
Input
Single-phase 230 V, 7.4 kW, PF 1; then 3-phase 400 V, 11 kW, PF 1
Output
32.17 A on one line for 7.4 kW; 15.88 A per line for 11 kW
A three-phase charger delivers about half as much power again while each conductor carries under half the current. Whether a house can take either depends on the size of its main fuse and the DNO's agreement, so check before buying.
9.5 kW electric shower
Input
Single-phase 230 V, 9.5 kW, PF 1
Output
41.3 A
An instantaneous shower is a pure resistive load, so kW and kVA are the same. At over 40 A it needs its own radial circuit sized under BS 7671, and a large share of a typical house supply while it runs.
Measured 60 A per phase on a sub-main
Input
3-phase 400 V, 60 A, PF 0.9
Output
41.57 kVA, 37.41 kW, 18.12 kVAR
Clamp-meter readings on each phase convert directly to kVA. Do this per phase if the readings differ, because the formula assumes a balanced load.
Background and insight
For a balanced three-phase load the apparent power is S = √3 × V(LL) × I, where V(LL) is the line-to-line voltage and I the current in each line. The √3 comes from the 120° spacing of the phases: the voltage between two lines is √3 times the voltage from a line to neutral, and three phases each carry V(LN) × I, so S = 3 × V(LN) × I = √3 × V(LL) × I. Single-phase is simply S = V × I.
Real power, the part that does work and that a kWh meter bills, is P = S × PF. Reactive power, which circulates between the supply and the magnetic fields of motors and transformers, is Q = S × sin φ, where φ = arccos PF. Cables, breakers and transformers must carry the full current, so they are rated in amps or kVA, not kW. A 100 A load at 480 V and PF 0.85 is 83.1 kVA but only 70.7 kW.
Motor nameplates give output power in horsepower or kW at the shaft. The electrical input is the output divided by efficiency, so a 10 hp motor (7.457 kW) at 90% efficiency draws 8.29 kW from the supply. One horsepower is 745.7 W (NIST SP 811). For wiring and protection the NEC uses its own full-load current tables (430.248 for single-phase, 430.250 for three-phase) rather than nameplate amps, because they are deliberately conservative.
Common use cases
Feeder and breaker checks
Convert a kW or kVA schedule into amps to choose cables, breakers and busbars.
Motor circuits
Estimate the running current of a pump, fan or compressor from its horsepower, efficiency and power factor.
Generator and UPS loading
Turn measured amps into kVA and kW to compare with a generator or UPS rating.
Reading meter data
Make sense of a power analyser reading by relating amps, kW, kVA and kVAR.
Tips and limitations
- The legal supply tolerance in Great Britain is 230 V plus 10% or minus 6%, so a nominal 230 V can sit anywhere between 216.2 V and 253 V. Calculate at the nominal 400/230 V and treat the result as a design figure, not an exact reading.
- For a motor, use "Motor rated output (kW)". Entering the plate kW as "Real power" would understate the current by the efficiency, about 10% on a 7.5 kW machine.
- Old drawings and some equipment still quote 415/240 V. Enter the voltage that is actually on the drawing; the difference is about 4% in current.
- If one phase is much more heavily loaded than the others, work out each phase on its own at 230 V and add the powers.
Sources and further reading
- The Electricity Safety, Quality and Continuity Regulations 2002, regulation 27, legislation.gov.uk. Declared low-voltage supply of 230 V (+10%, -6%) at 50 Hz (±1%) in Great Britain.
- BS 7671: Requirements for Electrical Installations (IET Wiring Regulations), The Institution of Engineering and Technology. The UK standard for designing and verifying electrical installations.
- Electricity at work: Safe working practices (HSG85), Health and Safety Executive. Duties when working on or near electrical systems.
Frequently asked questions
Is UK three-phase 400 V or 415 V?
The declared low-voltage supply in Great Britain is 230 V between line and neutral, with a permitted variation of 10% above and 6% below (Electricity Safety, Quality and Continuity Regulations 2002, regulation 27). The matching line-to-line voltage is √3 × 230 = 398 V, written as 400 V. Older equipment and drawings may still say 415 V from the former 240 V standard.
How many amps does a 7.5 kW motor draw on three-phase?
At 400 V, with a nameplate efficiency of 90% and power factor of 0.84, about 14.3 A per line. Pick "Motor rated output (kW)" and enter your motor's own figures, because efficiency and power factor vary with size, speed and load.
Should I convert kW to hp first?
No. UK and European motors are rated in kW of shaft output, and the calculator accepts that directly. The horsepower option is there for imported or older North American equipment.
Is a three-phase supply worth it for an EV charger at home?
Only if you already have a three-phase supply or the DNO will provide one at a sensible cost. An 11 kW three-phase charger draws 15.9 A per line, while a 7.4 kW single-phase charger draws 32.2 A on one line. The single-phase unit suits most overnight charging; the faster one matters mainly for cars that can accept 11 kW on AC.
What frequency should I use?
The declared frequency in Great Britain is 50 Hz, allowed to vary by 1% either way. This calculator does not need a frequency, but the power factor and capacitor tools do.
Can I use the result to size a cable?
It gives you the design current, which is the starting point. Cable size then follows BS 7671: the installation method, grouping, ambient temperature, protective device and voltage drop all come into it. Have a qualified electrician design and certify the circuit.
Is there an in-depth guide to the Three-Phase Power Calculator?
Yes. “The Three-Phase Power Formula: Where √3 Comes From” covers the background, how it works, common pitfalls and worked examples. Read the full guide.