Transformer Sizing Calculator (UK, IEC ratings)

Size a 50 Hz transformer from kW, kVA or amps, round up to an IEC rating such as 500, 630 or 800 kVA, and get full-load currents at 11 kV and 400 V.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Transformer Sizing Calculator?

A site that takes its supply at high voltage, or a private network that steps 11 kV down to 400 V, needs a transformer rated in kVA from the IEC 60076 series: 315, 400, 500, 630, 800, 1,000 kVA and so on. This version starts on that list and on 400 V, the British three-phase low voltage.

Give it the demand in kW with a power factor, in kVA or as measured amps. It adds a growth margin, picks the next IEC rating and shows the primary and secondary full-load currents. A 380 kW load at 0.9 with 20% spare needs 507 kVA, which is just over 500, so the answer is a 630 kVA unit carrying 909 A on its 400 V side.

Those currents are what the low-voltage switchboard, the incoming circuit breaker and the tails from the transformer are sized around, so it helps to see them next to the rating.

  • Load from kW and PF, kVA or amps
  • Spare capacity and next standard rating (ANSI or IEC lists)
  • Primary and secondary full-load and actual load currents
  • Voltage (turns) ratio
  • Comparison table of neighbouring sizes
Read the guide: Transformer Sizing: kVA, Full-Load Amps and Standard Ratings

Updated

How to use the Transformer Sizing Calculator

  1. Choose single-phase or three-phase.
  2. Enter the load as kW with power factor, as kVA, or as amps at the secondary voltage.
  3. Set the spare capacity you want, for example 20% for growth.
  4. Enter the primary and secondary voltages (line to line for three-phase) and choose North American or IEC ratings.
  5. Read the standard size, how heavily it is loaded today, the full-load currents and the voltage ratio.

Worked examples

11 kV to 400 V for a distribution warehouse

Input

Three-phase, 380 kW at PF 0.9, 20% spare, 11,000 V to 400 V, IEC ratings

Output

422.2 kVA load, 506.7 kVA required, 630 kVA (67% loaded); 33.1 A at 11 kV, 909.3 A at 400 V

The next size down, 500 kVA, falls short of 506.7 kVA by under 2%. Some designers would accept it with a tighter spare margin; the table under the result shows its loading so you can judge.

Rating on a 433 V no-load secondary

Input

As above but secondary entered as 433 V

Output

630 kVA; 840.0 A full-load at 433 V

If the data sheet gives a 433 V open-circuit secondary, enter that: the extra voltage allows for the drop on load. The rated current quoted at 433 V is about 8% lower than at 400 V, so compare like with like.

Isolating transformer for a 60 kW machine

Input

Three-phase, 60 kW at PF 0.85, 25% spare, 400 V to 400 V, IEC ratings

Output

70.6 kVA load, 88.2 kVA required, 100 kVA (71% loaded); 144.3 A each side

A 1:1 ratio is common where a machine needs its own earthing arrangement or isolation from the rest of the installation.

Background and insight

Transformers are rated in kVA rather than kW because their heating depends on current and voltage, not on the power factor of the load. Full-load current is I = kVA × 1000 ÷ V for single-phase and I = kVA × 1000 ÷ (√3 × V(LL)) for three-phase. A 75 kVA three-phase unit stepping 480 V down to 208Y/120 V carries 90.2 A on the primary and 208.2 A on the secondary.

The load figure should be the calculated demand, after any diversity your code allows, not the sum of nameplates. Designers then add spare capacity, commonly 20 to 25%, so that the unit runs at about 80% of its rating today. That margin covers growth, keeps losses and temperature rise down, and leaves room for motor starting. Harmonic-rich loads (computers, drives, LED drivers) may need a K-factor rated transformer or a further derating.

For an ideal transformer the voltage ratio equals the turns ratio, a = Vp ÷ Vs = Np ÷ Ns, and current goes the other way: Is = Ip × a. In three-phase units the per-winding ratio depends on the connection; a delta-wye 480 to 208Y/120 V transformer has 480 V on each delta winding and 120 V on each wye winding, a winding ratio of 4:1, even though the line-to-line ratio is 2.31:1. Ratings follow ANSI/IEEE C57.12 series standards in North America and IEC 60076 elsewhere; protection follows NEC 450.3 or your local code.

Common use cases

  • Specifying a step-down transformer

    Choose the kVA for a 480 to 208/120 V panel feeding receptacles and lighting.

  • Machine isolation transformers

    Size a control or isolation transformer for imported equipment that needs a different voltage.

  • Checking an existing unit

    See how loaded a transformer is by entering the measured secondary amps.

  • Planning protection

    Get primary and secondary full-load amps as the starting point for breakers and conductors.

Tips and limitations

  • In Great Britain, power transformers of 1 kVA and above used on 50 Hz networks fall under the ecodesign regulation (EU) No 548/2014, now assimilated (formerly retained) EU law, which sets maximum losses. Ask suppliers for compliant units.
  • Use the after-diversity maximum demand for the load, not the sum of nameplates, or the transformer will run lightly loaded with its fixed core losses all year.
  • Check that the low-voltage cable from the transformer to the main switchboard can carry the full-load current, not only today's load.
  • Primary and secondary protection should be coordinated with the DNO's protection at the point of supply; agree settings with them early.

Sources and further reading

  1. Commission Regulation (EU) No 548/2014: ecodesign requirements for power transformers (assimilated, formerly retained, EU law), legislation.gov.uk. Scope: power transformers of 1 kVA and above in 50 Hz networks, with listed exclusions.
  2. The Electricity Safety, Quality and Continuity Regulations 2002, regulation 27, legislation.gov.uk. Declared 230 V, 50 Hz low-voltage supply in Great Britain.
  3. IEC 60076-1 Power transformers: General, International Electrotechnical Commission
  4. BS 7671: Requirements for Electrical Installations, The Institution of Engineering and Technology

Frequently asked questions

What sizes do transformers come in, in the UK?

Pick "IEC 60076 (R10 series)" and the calculator rounds up within 25, 50, 63, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,600, 2,000, 2,500 and 3,150 kVA. Check the maker's catalogue for what is built at your voltages, since not every rating is stocked.

How many amps is a 1,000 kVA transformer at 400 V?

1,000,000 ÷ (√3 × 400) = 1,443 A on the 400 V side. At an 11 kV primary it is 52.5 A. Set the load to 1,000 kVA with no spare to check any rating this way.

Why do some data sheets say 433 V instead of 400 V?

Because the secondary is rated at no load. The extra 8% allows for the voltage drop inside the transformer and in the cables, so the board sees roughly 400 V when loaded. Enter whichever voltage your data sheet uses.

Do transformers have to meet efficiency rules in Great Britain?

Yes. Regulation (EU) No 548/2014 on ecodesign for power transformers is assimilated (formerly retained) EU law in Great Britain and covers transformers of 1 kVA and above used in 50 Hz transmission and distribution networks or industry, with exclusions such as welding, traction and instrument transformers.

Which standard covers the wiring on the 400 V side?

BS 7671, the IET Wiring Regulations. The transformer itself and the high-voltage side are outside its scope and are covered by the DNO's connection requirements and the transformer's own standards.

Is 80% loading the right target?

It is a common starting point, not a rule. A unit that will see load growth, high ambient temperatures in a plant room or many harmonic-producing loads may justify more margin; a site with a flat, well-known load may run closer to its rating.

Is there an in-depth guide to the Transformer Sizing Calculator?

Yes. “Transformer Sizing: kVA, Full-Load Amps and Standard Ratings” covers the background, how it works, common pitfalls and worked examples. Read the full guide.