Ventilation Duct Size Calculator (UK, l/s and mm)

Size round ventilation ducts in mm from extract rates in l/s: speed, Pa/m loss and the next EN size, checked against Approved Document F ducting rules.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Duct Size Calculator?

In the UK, house ventilation is specified in litres per second. Approved Document F Volume 1 (for England) asks for intermittent extract of 15 l/s from a bathroom, 30 l/s from a kitchen with a cooker hood that extracts outside, or 60 l/s without one, and sets a whole dwelling rate for MVHR from floor area and bedrooms (31 l/s for three bedrooms). This version takes those flows in l/s and sizes round duct in the 100, 125, 150 mm series that fans and MVHR units use.

Fan boxes are rated against back pressure, so the duct loss in Pa/m is what decides whether a 15 l/s bathroom fan still delivers 15 l/s at the outside wall. Under the 2021 edition, which applies now, ducts should be rigid wherever possible, and flexible duct is only for final connections of up to 1.5 m (paragraphs 1.76 to 1.77). Approved Document F Volume 1, 2026 edition, which takes effect on 24 March 2027, goes further: runs of no more than 2 m where practical, flexible duct only for 200 mm final connections, design calculations for longer runs, and MVHR static pressure limits in its Table 1.8.

  • Velocity and equal-friction sizing in US or metric units
  • Darcy-Weisbach with Colebrook friction and five roughness categories
  • Next standard round size in inch or EN 1506 metric series
  • Rectangular equivalents from the Huebscher formula with aspect ratio
  • Typical design velocity table and velocity pressure for fitting losses
Read the guide: Duct Sizing: The Velocity and Equal-Friction Methods Explained

Updated

How to use the Duct Size Calculator

  1. Choose SI, then set the airflow unit to L/s and type the rate from Approved Document F or the fan data sheet.
  2. For a single fan, use the velocity method (about 3 m/s keeps noise down); for an MVHR network, use equal friction at around 0.5 to 1 Pa/m.
  3. Pick the duct material: smooth for PVC or semi-rigid radial duct, flexible for any flex connection.
  4. Read the next standard size and its Pa/m, multiply by the run length and add fittings before comparing with the fan curve.

Worked examples

Bathroom extract fan, 15 l/s

Input

15 l/s in 100 mm smooth rigid duct, then in 100 mm flexible duct

Output

Rigid: 1.91 m/s, 0.65 Pa/m. Flexible: 1.31 Pa/m, twice the loss

This is why the guidance limits flexible duct to short final connections (up to 1.5 m under the 2021 edition that applies now). A small axial fan loses flow quickly against back pressure, so measure the flow at commissioning.

Kitchen with no ducted cooker hood, 60 l/s

Input

60 l/s, velocity 4 m/s, smooth duct

Output

138.2 mm exact, so 150 mm: 3.40 m/s, 1.08 Pa/m; a 125 mm duct would run at 4.89 m/s and 2.61 Pa/m

Fitting a 125 mm duct to a 60 l/s fan more than doubles the friction per metre. Rectangular 204 x 60 mm style ducting needs the same check using its equivalent diameter.

MVHR main for a three-bedroom house

Input

Whole dwelling rate 31 l/s (Table 1.3), equal friction 1 Pa/m, smooth duct

Output

119.4 mm exact, 125 mm standard at 2.53 m/s and 0.80 Pa/m

Approved Document F Volume 1, 2026 edition, which takes effect on 24 March 2027, caps the design static pressure of an MVHR system with a total flow up to 37 l/s at 60 Pa (Table 1.8), including the unit's filters, terminals and bends, so straight duct must use only part of it. Until then the 2021 edition applies, which has no such table; check the MVHR maker's fan curve.

Background and insight

The velocity method uses continuity alone: area equals airflow divided by velocity, so D = √(4Q/πV). It is simple and controls noise, but it ignores how much pressure the run will consume. The equal-friction method fixes the pressure loss per unit length instead, so every branch of a system loses pressure at a similar rate, which makes balancing easier. Residential designers commonly use 0.06 to 0.10 in.wg per 100 ft; ACCA Manual D derives the actual rate from the fan's available static pressure and the longest run.

Friction in a round duct follows the Darcy-Weisbach equation, Δp/L = (f/D)·ρV²/2. The friction factor f comes from the Colebrook equation, which depends on the Reynolds number and the relative roughness ε/D. ASHRAE classes galvanized steel ducts as medium smooth with ε = 0.09 mm (0.0003 ft), the basis of its friction chart, and lists smoother and rougher categories for other materials. Flexible duct, even fully stretched, is far rougher, and sagging or compressed flex can double the loss again.

A rectangular duct does not have the same friction as a round duct of equal area, because its corners add wetted perimeter. Huebscher (1948) gave the equivalent diameter that carries the same airflow at the same friction: De = 1.30 (ab)^0.625 / (a + b)^0.25. A 12 x 12 in duct is equivalent to 13.1 in round, not the 13.5 in its area would suggest. Aspect ratios above about 4:1 waste metal and pressure, and are best avoided.

Common use cases

  • Residential duct layouts

    Size trunks and branch runs for a furnace or heat pump from room airflows and a target friction rate.

  • Ventilation and extract systems

    Pick duct sizes for an MVHR unit, a bathroom fan run or a kitchen extract in metric or US units.

  • Swapping round for rectangular

    Find a rectangular section that fits a ceiling void or joist bay without losing airflow or adding friction.

  • Checking an existing duct

    Enter the airflow and see what friction and velocity a given round size produces, to explain noise or low airflow.

Tips and limitations

  • Approved Document F applies in England; Wales, Scotland and Northern Ireland publish their own ventilation guidance, so check the rates there.
  • Ducts through a loft must be insulated (at least 25 mm of insulation with conductivity 0.04 W/m·K or better) to stop condensation running back into the fan.
  • Each outside terminal should have a free area of at least 90% of its duct, so a louvred grille on a 100 mm duct can undo a good duct size.
  • From 24 March 2027, under the 2026 edition, a new fan in an existing home with more than 2 m of duct or more than one 90 degree offset should be flow-tested and the result recorded in l/s (paragraph 4.26).

Sources and further reading

  1. Approved Document F: Ventilation, Volume 1 Dwellings, 2021 edition (current), GOV.UK. Tables 1.1 to 1.3 (extract and whole dwelling rates); paragraphs 1.76 to 1.77 (rigid duct, flexible final connections up to 1.5 m).
  2. Approved Document F: Ventilation, Volume 1 Dwellings, 2026 edition, GOV.UK (MHCLG). Takes effect on 24 March 2027 (24 September 2027 for higher-risk work). Paragraphs 1.76 to 1.85 and Table 1.8 (ducting and static pressure), paragraph 4.26 (flow testing).
  3. Approved Document F (2026), GOV.UK
  4. Ventilation: Approved Document F, GOV.UK

Frequently asked questions

What size duct does a bathroom extractor fan need?

Most 15 l/s bathroom fans have a 100 mm spigot. In rigid 100 mm duct the air runs at about 1.9 m/s and loses about 0.65 Pa per metre, which is fine for a short run. Keep it rigid and as short as possible.

What size duct does a 60 l/s kitchen fan need?

In smooth rigid duct at about 4 m/s, 60 l/s needs 138 mm, so 150 mm: 3.40 m/s and 1.08 Pa/m. A 125 mm duct would run at 4.89 m/s and 2.61 Pa/m. The extract rates themselves are on the air changes calculator.

How do I convert m³/h to l/s?

Divide m³/h by 3.6. MVHR units are often rated in m³/h, so 150 m³/h is about 41.7 l/s. The calculator converts the figure when you switch the airflow unit.

How long can a bathroom fan duct be?

Under the 2021 edition of Approved Document F, which applies now, use rigid duct wherever possible and flexible duct only for final connections of up to 1.5 m. The 2026 edition, which takes effect on 24 March 2027, asks for rigid duct no longer than 2 m where practical, with design calculations for longer runs showing that the fan, ducting and terminal still achieve the required flow.

What static pressure is allowed for MVHR ductwork?

Approved Document F Volume 1, 2026 edition, which takes effect on 24 March 2027, sets the maximum design static pressure by total flow in Table 1.8: for MVHR, 60 Pa up to 37 l/s, 110 Pa from 38 to 53 l/s and 160 Pa from 54 l/s. The 2021 edition that applies until then has no Table 1.8, so design to the MVHR maker's fan curve.

Is there an in-depth guide to the Duct Size Calculator?

Yes. “Duct Sizing: The Velocity and Equal-Friction Methods Explained” covers the background, how it works, common pitfalls and worked examples. Read the full guide.