United Kingdom version. Metric rooms in metres, airflow in l/s and m³/h, and the whole dwelling rate from Approved Document F Volume 1 (England) instead of the US ASHRAE formula. US version
Air Changes per Hour and Part F Ventilation Calculator (UK)
Convert extract fan l/s to air changes per hour for a room, find the purge rate of four ACH, and work out the Part F whole dwelling ventilation rate for your home.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Air Changes per Hour Calculator?
Ventilation for homes in England is set out in Approved Document F Volume 1, and it speaks in litres per second rather than air changes. Extract fans have minimum rates (Table 1.1: 15 l/s for a bathroom, 30 l/s for a kitchen with a cooker hood ducted outside, 60 l/s without one), and the whole home needs a background supply rate of the higher of 0.3 l/s per m² of floor area and a figure set by the number of bedrooms (Table 1.3).
Air changes per hour still matter in two places. Purge ventilation, for clearing smoke or paint fumes, should manage at least four air changes per hour in each habitable room, usually through an opening window. And an internal bathroom with no outside wall should have an intermittent fan that extracts at four air changes per hour as well as meeting the l/s figure.
This version starts in metres, shows l/s next to m³/h, and switches the whole house panel to the Part F rule. A three-bedroom semi of 85 m² needs 31 l/s: the bedroom figure governs because 0.3 l/s per m² only gives 25.5 l/s.
- ACH from airflow or airflow from a target ACH
- Room volume from dimensions or entered directly, in feet or metres
- Airflow in cfm, m³/h and L/s together
- ASHRAE 62.2 whole-house ventilation rate from floor area and bedrooms
- Guidance table from CDC, ASHRAE 62.2, ASHRAE 170 and IECC with sources
Updated
How to use the Air Changes per Hour Calculator
- Enter the room in metres: length, width and ceiling height, usually about 2.4 m in a modern house.
- To check a fan, choose "ACH from airflow" and enter its rated flow in m³/h (l/s times 3.6).
- For purge ventilation, choose "Airflow for target ACH" and enter 4; the result gives the l/s an opening or fan must move.
- In the whole dwelling panel, keep the Approved Document F rule, enter the internal floor area of all storeys and the number of bedrooms.
Worked examples
A 15 l/s bathroom fan in air changes
Input
Bathroom 2.2 x 1.8 x 2.4 m, fan 15 l/s (54 m³/h)
Output
9.5 m³; 5.68 ACH, one air change every 10.6 minutes
15 l/s is the Table 1.1 minimum for an intermittent bathroom fan. On a continuous system the bathroom high rate is 8 l/s (Table 1.2), 3.03 ACH in this room; the four-ACH rule in paragraph 1.48 applies to intermittent fans in rooms with no external wall.
Purge ventilation for a lounge
Input
Lounge 4.5 x 3.6 x 2.4 m, target 4 ACH
Output
38.9 m³; 155.5 m³/h = 43.2 l/s
Approved Document F asks for four air changes an hour of purge in each habitable room. That is normally met with an opening window of the size in its Table 1.4 rather than a fan.
Whole dwelling rate for two homes
Input
3-bedroom semi, 85 m²; 2-bedroom flat, 150 m² over two levels
Output
Semi: 31 l/s (bedrooms govern; 0.3 l/s per m² gives 25.5); large flat: 45 l/s (area governs; Table 1.3 gives 25)
The rule takes whichever is higher, so large homes with few bedrooms are sized by floor area. With 2.4 m ceilings, 31 l/s in the semi is about 0.55 air changes per hour.
Background and insight
ACH is a convenient way to compare rooms of different sizes, but it is not how every standard sets ventilation. ASHRAE 62.1 for commercial buildings gives outdoor air per person plus per square foot of floor, and ASHRAE 62.2 for homes uses 0.03 cfm per square foot of floor area plus 7.5 cfm for each occupant, counting bedrooms plus one. A 1,500 ft² three-bedroom house needs 75 cfm of continuous ventilation, which is only about 0.35 ACH.
Higher figures appear where airborne contaminants matter. In 2023 the CDC and NIOSH recommended aiming for 5 or more air changes per hour of clean air in occupied rooms, counting outdoor air, filtered return air and portable air cleaners together. Healthcare design under ASHRAE 170 sets 12 ACH for new airborne infection isolation rooms and 20 total ACH for operating rooms. Kitchens and bathrooms in homes get local exhaust under 62.2: a 100 cfm range hood or 5 ACH continuous for kitchens, and 50 cfm intermittent or 20 cfm continuous for bathrooms.
ACH50, measured with a blower door at 50 Pa, is a different number entirely. It describes airtightness under test pressure, not ventilation, and the 2021 IECC limits new homes to 3 ACH50 in most climate zones. Natural infiltration under normal conditions is a small fraction of the ACH50 value. With perfect mixing, each air change removes 63% of a contaminant, so 99% removal takes about 4.6 air changes.
Common use cases
Sizing portable air cleaners
Check whether a HEPA unit's CADR delivers 5 ACH in a classroom, office or bedroom, or how many units a large room needs.
Bathroom and kitchen fans
Turn a room volume into the fan cfm needed for a target number of air changes, then compare with the 62.2 minimums.
Whole-house ventilation
Get the ASHRAE 62.2 continuous rate for an ERV, HRV or exhaust-only system in a new or retrofitted home.
Workshops and spray booths
Estimate the extract airflow for a target ACH, then confirm against the solvent or dust guidance that applies.
Tips and limitations
- Fan rates on UK packaging are often quoted in m³/h; divide by 3.6 for l/s.
- Approved Document F asks for a 10 mm door undercut so extracted air can be replaced from other rooms.
- Approved Document F Section 4 asks for the installed air flow rates of mechanical systems to be measured and the results given to the building control body, using a commissioning sheet like the one in its Appendix C.
Sources and further reading
- Approved Document F: Ventilation, Volume 1 dwellings (2021 edition), GOV.UK. Tables 1.1 to 1.3 (extract and whole dwelling rates), paragraph 1.24 (0.3 l/s per m²; 1.20 in the 2026 edition), 1.27 (purge at four air changes per hour) and 1.48 (wet rooms without external walls). The 2026 edition, in force from 24 March 2027, keeps the same rates.
- Building regulations approval, GOV.UK
Frequently asked questions
What extract rate does a bathroom fan need under Part F?
An intermittent bathroom fan needs at least 15 l/s (Approved Document F Volume 1, Table 1.1). On a continuous mechanical extract system each bathroom needs a high rate of at least 8 l/s (Table 1.2). A WC alone needs 6 l/s.
What extract rate does a kitchen need in England?
30 l/s if a cooker hood extracts to the outside, or 60 l/s for a wall or ceiling fan where there is no ducted hood. A recirculating hood on its own does not count as ventilation. A continuous system needs a kitchen high rate of 13 l/s.
How do I work out the whole dwelling ventilation rate?
Take the higher of 0.3 l/s per m² of internal floor area (all storeys added together) and the Table 1.3 figure: 19, 25, 31, 37 and 43 l/s for one to five bedrooms, plus 6 l/s for each further bedroom. A home with a single habitable room uses 13 l/s.
What does four air changes per hour mean in Part F?
It is the purge rate for habitable rooms: enough airflow to replace the room air four times an hour to clear smoke, fumes or odours quickly. Wet rooms with no outside wall should also have a fan that extracts at four air changes per hour.
How many l/s is 100 m³/h?
27.8 l/s. Divide m³/h by 3.6 to get litres per second, and multiply l/s by 3.6 to get m³/h.
Does Approved Document F apply in Wales, Scotland and Northern Ireland?
No. These figures are for England. Wales has its own Approved Document F, Scotland uses the Building Standards Technical Handbook Section 3, and Northern Ireland uses Technical Booklet K, so check the guidance for where you are building.
Is there an in-depth guide to the Air Changes per Hour Calculator?
Yes. “Air Changes per Hour: What ACH Means and How Much Ventilation You Need” covers the background, how it works, common pitfalls and worked examples. Read the full guide.