United Kingdom version. Sizes UK copper tube to BS EN 1057 Table X (15, 22, 28 mm and up) in litres per second, metres and kPa, with the head a gravity system can spare. US version
Water Pipe Size Calculator: 15, 22 or 28 mm Copper (UK)
Choose 15, 22 or 28 mm copper (BS EN 1057 Table X) from a flow in l/s: bore in mm, water speed and the pressure lost per metre, for mains or gravity-fed systems.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Water Pipe Size Calculator?
British plumbing is run in metric copper sized by its outside diameter: 15 mm to taps and radiators, 22 mm for the cold main and cylinder feeds, 28 mm where several outlets draw at once. The tube most merchants stock is the BS EN 1057 Table X range, which has thin walls (0.7 mm on 15 mm, 0.9 mm on 22 and 28 mm), so the bores are 13.6, 20.2 and 26.2 mm. This version picks from that series, not from American nominal sizes.
What decides the size in a UK house is usually the pressure available rather than speed alone. A combi boiler or unvented cylinder runs on mains pressure, but a vented cylinder fed from a cold water cistern in the loft may have only 1 to 3 m of head at the bath taps. Put in a flow in l/s and a velocity limit, then read the loss per metre to check the run against the head you actually have.
- Minimum inside diameter from flow and maximum velocity
- Published inside diameters for copper L and M, PEX SDR 9, PVC and steel Schedule 40
- Actual velocity and Hazen-Williams friction loss with editable C
- Total loss over a length in psi, kPa and head
- Side-by-side comparison of every material for the same flow
Updated
How to use the Water Pipe Size Calculator
- Keep the unit system on SI and the tube standard on UK (BS EN 1057 copper).
- Enter the flow the pipe must carry in l/s: one outlet for a branch, or the outlets likely to run together for a main.
- Set a maximum velocity. Lower speeds are quieter and lose less head.
- Enter the length of the run, then add an allowance for elbows and tees before comparing the loss with the head or pressure available.
Worked examples
Gravity-fed bath: why 15 mm is not enough
Input
0.3 l/s, 20 m run, Table X copper, C 140; velocity limit 2.4 m/s, then 1.5 m/s
Output
15 mm: 2.07 m/s and 8.33 m of head lost; 22 mm: 0.94 m/s and 1.21 m lost
Both sizes pass a velocity check at 2.4 m/s, but a loft cistern 2 m above the taps cannot overcome 8.3 m of friction in 15 mm tube. The 1.5 m/s limit picks 22 mm, which leaves some head for the tap itself.
Cold main feeding an unvented cylinder
Input
0.6 l/s, 15 m from the stop tap, 1.5 m/s limit
Output
Minimum bore 22.57 mm, so 28 mm (26.2 mm bore): 1.11 m/s, 9.07 kPa lost
The same flow in 22 mm would run at 1.87 m/s and lose 32.2 kPa over 15 m. Unvented cylinder makers state the dynamic pressure and flow they need at the inlet, so the loss matters as much as the speed.
A single basin tap
Input
0.15 l/s, 8 m of 15 mm
Output
13.6 mm bore, 1.03 m/s, 9.04 kPa lost (0.92 m of head)
For one outlet on mains pressure, 15 mm is comfortable. On a low-head gravity supply even this short branch takes nearly a metre of head.
Background and insight
Nominal sizes are not inside diameters. Copper tube to ASTM B88 has an outside diameter 1/8 in larger than its nominal size, and type K, L and M differ only in wall thickness, so type M has the largest bore. PEX to ASTM F876 uses the same copper tube sizes (CTS) outside but a much thicker SDR 9 wall, so 3/4 in PEX has an inside diameter of only about 0.68 in. Schedule 40 PVC and steel pipe follow the iron pipe size system, where 3/4 in nominal has a 1.050 in OD and a 0.824 in ID.
Velocity limits protect against noise, water hammer and erosion of the pipe wall. The Copper Development Association and the Uniform Plumbing Code limit copper systems to 8 ft/s (2.4 m/s) for cold water and 5 ft/s (1.5 m/s) for hot water, and the CDA recommends 2 to 3 ft/s above 140 °F, where erosion corrosion is faster. Many designers keep residential branches nearer 4 ft/s for quiet.
Friction loss here uses the Hazen-Williams formula, an empirical fit for water at ordinary temperatures in turbulent flow. Its roughness constant C is about 150 for new plastic pipe, 140 for copper, 120 for new steel and 100 or less for old corroded steel. In US units, head loss per 100 ft = 0.2083 (100/C)^1.852 x gpm^1.852 / d^4.8655. Because loss scales with almost the fifth power of diameter, going up one pipe size typically cuts friction by more than half.
Common use cases
Residential water service and mains
Check that a service line or main carries the peak demand without exceeding the velocity limit or losing too much pressure.
Copper to PEX substitutions
See which PEX size matches the bore of an existing copper line before a repipe.
Hydronic and process loops
Pick a pipe size for a circulator flow at a target velocity, then read the head loss for pump selection.
Irrigation and outbuildings
Size a PVC run to a garden, barn or workshop and estimate the pressure left at the far end.
Tips and limitations
- Table Y tube (for example 15 x 1.0 and 22 x 1.2 mm) has thicker walls and a slightly smaller bore; switch the C value or the length if you are checking it against Table X figures.
- On a vented system, measure the head from the water level in the cold cistern to the outlet. That height is all the pressure you have.
- Microbore (8 and 10 mm) and plastic push-fit pipe have different bores; check the maker's data sheet rather than using copper figures.
- Water fittings must conform to a British Standard or an approved specification under the Water Fittings Regulations, so buy marked tube and fittings.
Sources and further reading
- The Water Supply (Water Fittings) Regulations 1999, regulation 4, legislation.gov.uk. Every water fitting must be of an appropriate quality and standard, conforming to a British Standard or an approved specification.
- Copper tube size ranges (BS EN 1057 Black Label, Table X), Wednesbury Tube (Mueller Europe). Dimensions per BS EN 1057, as published by the maker: outside diameter, wall and temper for 15 x 0.7, 22 x 0.9, 28 x 0.9, 35 x 1.2, 42 x 1.2, 54 x 1.2, 67 x 1.2 and 76 x 1.5 mm tube.
Frequently asked questions
What is the inside diameter of 15 mm and 22 mm copper pipe?
For BS EN 1057 Table X tube (the common half-hard grade), 15 x 0.7 mm has a 13.6 mm bore and 22 x 0.9 mm has a 20.2 mm bore. 28 x 0.9 mm is 26.2 mm inside.
Should I run 15 mm or 22 mm to a bath?
On a gravity-fed system, 22 mm almost always: at 0.3 l/s a 20 m run of 15 mm loses about 8 m of head, far more than a loft cistern provides. On a combi or unvented system 15 mm can work for short runs, but check the loss against the pressure the boiler or cylinder needs.
When do I need 28 mm copper in a house?
When one pipe feeds several outlets that run together, such as the cold main to an unvented cylinder and the rest of the house. At 0.6 l/s, 28 mm loses about 9 kPa in 15 m against 32 kPa for 22 mm.
What is the difference between Table X and Table Y copper?
Both are BS EN 1057 tube. Table X (formerly BS 2871 Table X) has the thinner walls used for most above-ground plumbing and heating; Table Y has thicker walls and is used where extra strength is needed, such as underground or in coils.
How much head does 1 metre of water give?
About 9.8 kPa, or 0.098 bar. A cistern 2 m above a tap gives roughly 0.2 bar before any friction, which is why gravity systems need generous pipe sizes.
Can I use this for central heating pipework?
Yes for the pipe itself, if you know the flow in l/s from the radiator outputs and the flow-return temperature difference. Remember that water near 70 °C is less viscous, so Hazen-Williams slightly overstates the loss in hot pipes.
Is there an in-depth guide to the Water Pipe Size Calculator?
Yes. “Water Pipe Sizing by Velocity and Hazen-Williams Friction Loss” covers the background, how it works, common pitfalls and worked examples. Read the full guide.
Related Tools You May Like